I get what you’re saying, but without a monitoring device on the actual supply to the garage, it isn’t physically possible for the Zappi to know what the garage load is and adjust accordingly.I have a Harvi with CT clamp on the main supply in the house. This reports as the total energy on the Zappi (the Zappi is paired with the Harvi for this).
However, the garage, where the Zappi is, is on a supply from the house (32amp). I think the Zappi itself is detecting the power load in the garage and adjusting the EV charge accordingly.
Is there an additional wireless or wired monitor going from the zappi to the garage supply?
It’s quite possible, I know nothing about the zappi, but I’d be surprised if they’ve built in the functionality to allow more than one current monitoring device.
Thinking about it, if your installing electrician was more worried about the load on the garage supply, they could’ve put this Harvi device in the fusebox on the garage supply cables rather than the main incoming supply cables.
Further thinking about it(!) I thought a properly compliant installed 7kWh had to be on a dedicated circuit from the consumer unit?