I have several heatpumps, 13 x air to air and 1 x air to water (14kW). How much power does a typical heat pump require is not a good question, too many variables - outside air temp, inside temp reqd, insulation etc etc. The way I approached it was to take a year of gas bills, with a guestimate of boiler efficiency (89%) for mine it was possible to work out the heat input requirements for my property and comfort levels etc. The performance of the heatpump (COP) is known and published. Armed with this data divide the heat input required by the COP divided by 100 this will give you the electrical input you need.Good question. I'm looking for someone with a heat pump to compare running costs with the Tepeo ZEB.
Example
Heat Input = 12,000 kWh
Boiler Efficiency = 90%
Heatpump COP = 420
From the gas bill heatinput shows 12000 kWh with an efficiency of 90% the gas purchased would be 12000 x 1.1 = 13333.33 kWh of gas 7.3p = £973.31
Heatpump
Heat input reqd 12000kWh with an efficiency between 250% & 530% :
COP 250% - 12000 kWh required = 12000 / (250 / 100) = 4800 kWh
Tariff average say 12p = 4800 x .12 = £576
COP 530% - 12000 kWh required = 12000 / (530 / 100) = 2264 kWh
Tariff average say 12p = 2264 x .12 = £271
Tepeo will be 100% efficient and can be run on off peak only.
Tomato off peak is 5p kWh, 12000kWh cost would be 120000 x 0.05= £600
As expected, the heatpump is cheaper even at the lower end of the performance specification. To get the best COP from a heatpump generally the flow temperatures' are tuned for best performance. The flow temperature is lower than that of a gas boiler. I did a trial with my system running the boiler at 35 degC flow temp and left it running24/7 for a week. The house was definitely more comfortable and it proved my house with it's radiator sizes and insulation would be fine. The Tepeo will run at normal boiler temperatures.
Im sure some 'experts' will argue my calculations above arent valid but I assure you in my case they worked really well and were just about on the button.